100kVA Dry Transformer
1. Energy Efficient: Low loss design ensures significant energy savings and cost efficiency.
2. Flame Retardant & Explosion-Proof: Safe, pollution-free, and maintenance-free, reducing expenses and enabling installation near load centers.
3. Low Noise: Optimized design and high magnetic conductivity materials effectively lower noise levels.
4. Strong Overload Capability: F-class rating ensures excellent heat resistance and reliable performance under overloading.
5. Easy Maintenance: Oil-free design allows for re-energization after long-term shutdown, simplifying upkeep.
6. Durable Enclosure: Robust casing with excellent heat dissipation and flexible wiring configurations.
Product Details
The SCB12-100kVA Dry Transformer is a highly reliable, safe, and efficient power distribution solution, specifically designed to operate without transformer oil. This makes it an ideal choice for indoor and environmentally sensitive applications where reducing environmental impact is a priority.
Key Features
Safe and Flame Retardant:
This transformer is designed to be pollution-free, explosion-proof, and boasts a high flame-retardant rating, ensuring safe operation in various industrial and commercial settings.
Energy Efficiency:
The SCB12-100kVA offers low loss, low noise, and low temperature rise, resulting in significant energy savings and optimal operational performance.
Strong Overload Capacity:
Equipped with F-class insulation, this transformer excels in heat resistance, ensuring stable and reliable performance even under heavy load conditions.
Moisture and Dust Resistance:
The coils are designed to resist moisture and dust, providing long-term reliability, especially in harsh environments. It also has high mechanical strength, making it durable under challenging conditions.
Low Maintenance:
With its oil-free design, the SCB12-100kVA transformer requires less maintenance, and it can be re-energized after long-term shutdowns without the usual hassle of oil checks.
Durable Construction:
The transformer features epoxy resin-cast windings, which provide excellent short-circuit resistance, impact toughness, and outstanding lightning impulse performance.
Applications
The SCB12-100kVA Dry Transformer is ideal for various sectors that require safe, efficient, and low-maintenance power distribution solutions:
Industrial Plants: A dependable solution for industrial environments requiring continuous and stable power.
Commercial Buildings: Perfect for office buildings, shopping malls, hotels, and more.
Schools and Hospitals: Ensures consistent power for educational institutions and healthcare facilities.
Other Locations: Suitable for residential areas and other applications requiring minimal maintenance and high efficiency.
Specifications
*Technical Data for 10KV Three Phase Oil-Immersed Distribution Transformer
Rated Power (KVA) | High Voltage (KV) | Low Voltage (KV) | Vector Group | Short Circuit Dependence(%) | Loss(W) | No Load Current(%) | |
No-load Loss | Load Loss(W) | ||||||
30 | 4.16 12.47 13.2 13.8 24.94 34.5 | 0.208 0.4 0.6 | Dyn11 Yyn0 | 4 | 100 | 600 | 2.1 |
50 | 130 | 870 | 2 | ||||
63 | 150 | 1040 | 1.9 | ||||
80 | 180 | 1250 | 1.8 | ||||
100 | 120 | 1500 | 1.6 | ||||
125 | 240 | 1800 | 1.5 | ||||
160 | 280 | 2200 | 1.4 | ||||
200 | 340 | 2600 | 1.2 | ||||
250 | 400 | 3050 | 1.2 | ||||
315 | 480 | 3650 | 1.1 | ||||
400 | 570 | 4300 | 1 | ||||
500 | 680 | 5150 | 1 | ||||
630 | 4.5 | 810 | 6200 | 0.9 | |||
800 | 980 | 7500 | 0.8 | ||||
1000 | 1150 | 10300 | 0.7 | ||||
1250 | 1360 | 12000 | 0.6 | ||||
1600 | 1640 | 14500 | 0.6 | ||||
2000 | 5 | 1940 | 17400 | 0.6 | |||
2500 | 2300 | 20200 | 0.5 |
*20kV Epoxy-resin Insulation Dry-type Transformer
Rated Power (KVA) | Voltage Combined |
Vector No-load Group Loss(kw) | Under different insulation heat-resisting rank load loss(W) |
No-load Current (%) |
Short Circuit mpedance (%) | |||||
HV(KV) | High Pressurd Tapping | LV(KV) | 130℃(B) (100℃) | 155℃(B) (120℃) | 180℃(B) (145℃) | |||||
50 | 20 | ±2x1.25% ±5% | 0.4 | 340 | 1160 | 1230 | 1310 | 2 | 6.0 | |
100 | 540 | 1870 | 1990 | 2130 | 1.8 | |||||
160 | 670 | 2330 | 2470 | 2640 | 1.6 | |||||
200 | 730 | 2770 | 2940 | 3140 | 1.6 | |||||
250 | 840 | 3220 | 3420 | 3660 | 1.3 | |||||
315 | 970 | 3850 | 4080 | 4360 | 1.3 | |||||
400 | 1150 | 4650 | 4840 | 5180 | 1.1 | |||||
500 | Dynl1 Yyn0 | 1350 | 5460 | 5790 | 6190 | 1.1 | ||||
630 | 1530 | 6450 | 6840 | 7320 | 1 | |||||
800 | 1750 | 7790 | 8260 | 8B40 | 1 | |||||
1000 | 2070 | 9220 | 9780 | 10400 | 0.85 | |||||
1250 | 2380 | 10800 | 11500 | 12300 | 0.85 | |||||
1600 | 2790 | 13000 | 13800 | 14800 | 0.85 | |||||
2000 | 3240 | 15400 | 16300 | 17500 | 0.7 | |||||
2500 | 3870 | 18200 | 19300 | 20700 | 0.7 |